Case analysis of voltage common line in three-phase four-wire electric energy metering device

Jun 27, 2025 Leave a message

The wiring of three-phase four-wire electric energy metering devices is complex, and the types of abnormal wiring are diverse. If the abnormal type is misidentified, it will lead to wiring correction errors, thereby causing new wiring abnormalities. This paper takes the voltage collinearity wiring abnormality as an example, analyzes the reasons why such wiring abnormalities are prone to misjudgment, studies the abnormal characteristics of electrical parameters, and proposes a voltage collinearity wiring abnormality determination method that is suitable for actual engineering, helping metering personnel to accurately identify abnormal types, support on-site fault elimination, and improve the accuracy of metering business work.
Keywords: three-phase four-wire; electric energy metering device; voltage collinearity

 

Content:

1. Purpose of this article

2. Case description

3. Principle analysis
3. 1 Analysis of the causes of misjudgment

3.2 Typical abnormal characteristics

4.Conclusion

 

1. Purpose of this article
The correct wiring of the electric energy metering device is the basic condition for maintaining the accuracy of the electric energy metering results, and it is related to the fairness and justice of electricity bill settlement. Power grid companies carry out periodic on-site inspections, use on-site calibrators and other tools at the operation site of the metering device to draw the wiring phase diagram, and combine manual analysis to check the wiring status of the metering device to ensure accurate measurement.


The wiring of the three-phase four-wire electric energy metering device is complex, and the types of abnormal wiring are complex and diverse. If the type of wiring abnormality is misjudged, it may lead to wiring correction errors, thereby causing new wiring abnormalities. Taking a case of repeated wiring abnormality as an example, this article analyzes the judgment method of wiring abnormalities such as voltage co-line and the causes of error correction, helping metering personnel to accurately judge the abnormality type and help improve quality and efficiency.

 

2. Case description
During the periodic on-site inspection, the metering personnel found that the wiring of a certain electric energy metering device was wrong in combination with the wiring phase diagram. After correction on site, the subsequent inspection found that the wiring of the device was still wrong and the error characteristics changed, that is, the wiring abnormality type changed.

info-303-152

After the wiring is changed, the current phasor is further characterized in the form of scattered points, and the wiring phasor diagram for the whole day is drawn. From the graph, the user's load is stable, phases A and C are inductive loads, and the power factor angle is always around 60°, while the power factor angle of phase B is around 0°, jumping between capacitive and inductive.

info-303-152

 

info-303-152

3. Principle analysis


3. 1 Analysis of the causes of misjudgment

The voltage, current, and voltage-current angle measured by the three components are shown in the table below. 

info-658-238

In the table, the power factor angle of 179.2° measured by the second element actually represents the angle between U1 and U2. Considering that the angle between U1 and U2 is 120°, the angle between U2 and I2 is actually 59.2°. At this time, the measurement results represent that the properties of the three-phase load are basically consistent, and all show the inductive load characteristics with a power factor angle of about 60°, which is in line with the common user power consumption characteristics.

info-303-152

 When the metering personnel made corrections on site, they reversed the current of phase B, so the electrical wiring diagram after correction:

info-303-152

3.2 Typical abnormal characteristics
In the current energy metering related specifications, for three-phase four-wire energy metering devices, only the phase voltage is designed in the voltage metering circuit, and the phase-to-phase voltage is not used as a conventional metering object, so the line voltage and angle cannot be obtained remotely. This characteristic parameter often requires metering personnel to go to the site for measurement, and then help determine whether voltage collinearity occurs. During remote diagnosis, metering personnel can restore the actual wiring phasor diagram based on the suspected voltage collinearity phase, combined with the electrical characteristics of the three-phase voltage phasors with an angle of 120°, to assist in supporting the judgment results.


4. Conclusion
The application of digital twin technology can achieve precise investment in power systems, improve the accuracy and feasibility of investment decisions, reduce investment risks, and achieve sustainable development of power systems. With the continuous advancement of technology and the deepening of application research, it is believed that the application of power system digital twin technology in precise investment will be more widely promoted and applied, providing greater support and guarantee for the development of power systems. 